SECTION 12: ELECTRIC DISCHARGE LAMP INSTALLATIONS
SECTION 12 ELECTRIC DISCHARGE LAMP INSTALLATIONS
A fireman’s emergency switch shall be provided for
- Exterior Electric Discharge lighting installations and/or
- Interior Electric Discharge lighting installations which run unattended (window lighting for display purposes).
Every fireman’s switch shall -
- Be arranged to isolate the installation from all poles of the supply, except that it need not isolate the installation from the neutral conductor of a 3-Phase 4-wire supply.
- Be coloured red and have fixed near it a nameplate marked with the words " FIREMAM’S SWITCH' in English and Arabic. This plate should be of minimum size 150 mm by 100 mm with lettering not less than 15 mm high.
- Have its "on and Off' positions clearly indicated by lettering legible to a person standing on the ground.
- It shall be fixed in a conspicuous position, reasonably accessible to firemen, and not more than 2.75 metres from the ground.
- For exterior installations it shall be outside the building and adjacent to the electric discharge lamps(s), or alternatively a notice indicating the position of the switch shall be placed adjacent to the electric discharge lamp(s).
- For interior installations, it shall be in the main entrance to the building or alternatively in a position to be agreed with the local fire-brigade authority.
- The voltage to earth shall not exceed 5 KV.
|
|
|
|
 |
|